摘要 通过对真空灭弧室击穿电压的测量及电场强度的计算,拟合出了真空灭弧室在小间隙下的击穿电压与间隙的关系式。并结合配永磁机构的真空断路器关合时的动特性,对10kV系统与35kV系统的电容器组进行关合时,考虑到断路器合闸时间的分散性,在一定合闸速度下,确定了关合涌流为最小的最佳预期关合点。 This paper describes the closing velocity and the pre-strike of vacuum circuit breaker in the synchronous closing. The expression of the gap withstand voltage vs. the gap separation between the two contacts of vacuum circuit breaker was derived from the experiments and the calculations. A critical velocity was proposed by calculation respectively for 10kV and 35kV. If the velocity were lower than the critical one, the pre-strike would happen when synchronous closing. The real closing point will be shifted from voltage zero due to pre-strike. If the velocity is higher than it, the circuit will be closed at zero voltage with no pre-strike. Taking into account the variation of the closing time, the prospective closing time is distinct with different closing velocity. Moreover, the optimal closing point will vary form system voltage and parameters, and closing velocity.
出处 《电工技术学报》 EI CSCD 北大核心 2004年第7期85-89,共5页 Transactions of China Electrotechnical Society
基金 国家自然科学基金资助项目(50007004)。
关键词 同步关合 预击穿 合闸速度 Synchronous closing,pre-strike,closing velocity
  • 相关文献

参考文献6

  • 1Delfino B, Fornari F, Gemme C, et al. Power quality improvement in transmission and distribution networks via synchronous switching. Transmission and Distribution Conference and Exposition, 2001(1):367-372
  • 2Lin K C, Chen N. Voltage-peak synchronous closing control for shunt capacitors. IEEE Proc. Gener. Transm.Distrib, 1998, 145, (3): 233-236
  • 3Carlo Cereda et al. Synchronous medium voltage circuit-breakers: ABB solution based on magnetic drive and electronic control. CIRED 99-15th Conference on Electricity Distribution, Nice, June 1999:13-21
  • 4You Yimin, Chen Degui, et al. The optimal design parameters selection of permanent actuator for vacuum circuit breaker based on dynamic characteristic analysis.XXth ISDEIV Proceedings, Tours (France) , 2002:584~587
  • 5Carlo Cereda etc. Synchronous medium voltage circuit-breakers: ABB Solution Based on Magnetic Drive and Electronic Control. CIRED 99-15th Conference on Electricity Distribution, Nice, June 1999:13-21
  • 6王季梅.真空开关[M].机械工业出版社,1982..

共引文献5

同被引文献245

引证文献22

二级引证文献214

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部