用丝束电极模拟研究混凝土中钢筋的锈蚀 被引量:2

Simulating Research on the Corrosion of Steel Bar in Concrete by Wire-Beam Electrode
在线阅读 下载PDF
导出
摘要 用丝束电极模拟混凝土中钢筋表面的不同位置,研究了浸于pH=12,浓度为10%的NaCl溶液中直至9 d的混凝土中钢筋的锈蚀状况.通过测量丝束电极的自然腐蚀电位、极化电阻、腐蚀电流,以及在丝束电极探头附近混凝土的密实性、孔溶液的pH值和Cl-含量的取样分析,研究了由于混凝土的不均匀性造成Cl-在其中扩散的不均匀性所致的钢筋锈蚀状况.结果表明:混凝土保护层越厚,则电极自然腐蚀电位越高,钢筋实际锈蚀状况也越轻;在混凝土密实性较高区域的孔溶液pH值相对较高,Cl-含量较低,由于该区域电极的自然腐蚀电位较高,因而电极的实际腐蚀状况较轻,而在混凝土密实性较低的区域,情况则刚好相反. The corrosion conditions of rebar embedded in the concrete which was immersed in 10% sodium chloride solution (pH = 12) for 9 d was studied by using the wire-beam electrode. Through measuring the natural corrosion potential, polarization resistance and polarization electric current, and analyzing the compactness of the concrete near the wire-beam electrode, the pH value of solution and the content of chloride ion, the corrosion conditions of reinforcing steel bar which was caused by heterogeneity in diffusion of chloride ion due to heterogeneity of the concrete was studied. The result shows that the thicker the protective layer of the concrete, the higher the natural corrosion potential of wire-beam electrode, which could alleviate the corrosion of the rebar. It is also found that the pH value is relatively higher and that the content of chloride ion is lower in dense areas of the concrete where the natural corrosion potential is higher, therefore the corrosion of reinforcing steel bar in this area is rather slight. While the other areas where the concrete is not dense, the things are opposite.
作者 施惠生 邓恺
出处 《建筑材料学报》 EI CAS CSCD 2005年第6期682-686,共5页 Journal of Building Materials
基金 上海市重点学科建设项目
关键词 混凝土 丝束电极 锈蚀 钢筋 concrete wire-beam electrode corrosion reinforcing bar
  • 相关文献

参考文献6

二级参考文献34

共引文献209

同被引文献13

引证文献2

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部