期刊文献+

ASVG在系统不对称情况下的运行及控制 被引量:9

Operation and control of ASVG under system asymmetric conditions
原文传递
导出
摘要 提出了一种控制ASVG(advancedstaticvargenerator)驱动脉冲的方法使ASVG装置发出正序电压的同时也产生负序电压,以抵消系统负序电压分量,抑制流过ASVG的负序电流。并用“开关函数”建模法给出了具体的控制算法。用该控制算法可使ASVG在系统出现15%的负序电压时仍能正常地工作而不过流。 ? In this paper, an approach controlling the triggering pulse of GTOs of advanced static var generator (ASVG) to generate a negative sequence voltage component while generating positive sequence voltage to counteract the system negative sequence component in order to suppress the negative sequence current through ASVG caused by system negative sequence voltage is presented. An algorithm to control the triggering pulse of ASVG is proposed based on modelling ASVG with “function of switchings” method. ASVG can operate normally and not overcurrent under a 15% negative sequence voltage component in system voltage with this control algorithm. Simulation results show that the analysis and algorithm are correct. 
出处 《清华大学学报(自然科学版)》 EI CAS CSCD 北大核心 1997年第7期26-29,共4页 Journal of Tsinghua University(Science and Technology)
关键词 静止无功发生器 电力系统 运行 GTO 不对称故障 advanced static var generator(ASVG) asymmetry negative sequence voltage component