摘要 为满足操作过电压设计限值的要求而使用合闸电阻存在诸多缺点,针对西北电网新建750 kV输电线路过电压水平,对沿线增设1组避雷器取代合闸电阻的想法进行了研究。以即将建成的兰州东-银川东750 kV输电线路工程为背景,利用电磁暂态计算程序(PSCAD/EMTDC)分别计算了沿线装设1组避雷器时,线路三相合空线、单相自动重合闸操作过电压水平。研究结果表明,不采取任何限制措施时,线路三相合空线和单相重合闸操作过电压标么值分别为1.94、2.01,超过线路设计要求1.80,而采用一组避雷器代替线路合闸电阻的方案后,则可改善线路过电压分布情况,并将过电压水平降至设计值1.80以下(三相合空线和单相重合闸操作过电压标么值分别为1.79、1.78)。 How to restrict the swithing overvoltage is discussed recently because of the 750 kV transmission line project in Northwest China. Idea of increasing only one group of arrester installed along line replacing with parallel resistance in breakers to suppress switching overvoltage in 750 kV transmission line is realized in this paper. Based on the 750 kV Lanzhoudong-Yinchuandong transmission line project, effects of the arrestor's position on switching overvoltages, including three phases energizing line without load, single phase auto-reclosing are calculated by using the electromagnetic transient program PSCAD/EMTDC. The result shows that without any arresters installed along line, the maximal overvoltage of three phases energizing line with no load (1.94per unit), single phase auto-reclosing (2.01 per unit) are higher than the design limit value (1.80 per unit). With the help of one arrester installed along line, the switching overvoltages(the maximal overvoltage of three phases energizing line with no load and single phase auto-reclosing are 1.79 and 1.78 per unit) are acceptable.
出处 《高电压技术》 EI CAS CSCD 北大核心 2008年第6期1105-1109,共5页 High Voltage Engineering
基金 国家自然科学基金(50737001)~~
关键词 750kV 输电线路 操作过电压 金属氧化物避雷器 避雷器位置 操作过电压沿线分布 通流容量 750 kV transmission line switching overvoltage MOA arrestor's position switching overvoltage distribution along line capacity of energy
  • 相关文献

参考文献16

  • 1Lgeate A C. Elimination of closing resistors on EHV circuit breakers[J]. IEEE Trans on Power Delivery, 1988, 3(1) : 223- 231.
  • 2印永华,房喜,朱跃.750kV输变电示范工程系统调试概况[J].电网技术,2005,29(20):5-13. 被引量:38
  • 3张健.福建500kV水莆泉线路操作过电压计算分析[J].福建电力与电工,2001,21(2):21-23. 被引量:3
  • 4衣立东,吕世荣.750kV输变电示范工程施工关键技术的研究与应用[J].电网技术,2006,30(3):51-56. 被引量:51
  • 5Riberiro J R. An application of metal oxide surge arresters in the elimination of need for closing resistors in EHV breakers[J]. IEEE Trans on Power Delivery, 1989, 4(1): 282-291.
  • 6亚历山大罗夫.超高压送电线路设计[M].北京:北京水利电力出版社,1987.
  • 7Eriksson A. Optimized line switching surge control using circuit breakers without closing resistors[C]// CIGRE 1990. Paris, France: CIGRE, 1990.
  • 8Rizk F A M. A model for Switching impulse leader inception and breakdown of long air-gaps[J]. IEEE Trans on PWRD, 1989, 4 (1): 596-605.
  • 9Rizk F A M. Switching impulse strength of air insulation: leader inception criterion[J]. IEEE Trans on PWRD, 1989, 4(4): 2187-2195.
  • 10Johns T, Eng C, Al-Rawi A M. Digital simulation of EHV systems under secondary arcing conditions associated with single-pole autoreclosure[J]. IEE Transm & Distrib, 1982, 29 (2) : 49-58.

二级参考文献58

共引文献147

同被引文献90

引证文献11

二级引证文献61

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部