国家大剧院水(冰)下玻璃廊围护结构空调负荷分析计算

Analysis and calculation of air conditioning load of underwater glass gallery envelope in the National Centre for the Performing Arts
在线阅读 下载PDF
导出
摘要 为保证国家大剧院水(冰)下玻璃廊冬季不结露,对围护结构外表面与室外空气和天空的对流和辐射换热量进行了分析研究,确定了室外空气综合温度的数值,并代替室外空调计算温度。分别对白天和夜间不同工况的传热计算和防结露计算进行了校核。推导了夏季水下玻璃屋顶围护结构冷负荷计算方法,计算出玻璃廊的冷负荷。介绍了玻璃廊的空调气流组织形式。 To prevent the underwater glass gallery from occurring condensation in winter, analyses the convection heat transfer between external surface of enclosure and outdoor air and radiation heat transfer between external surface of enclosure and sky, determines the value of outdoor sol-air temperature and use it in place of the outdoor air conditioning calculation temperature. Calculates and checks the heat transfer and condensation prevention in the day and night under different conditions. Deduces the calculation method of summer cooling load of the underwater glass gallery envelope and calculates this part of cooling load. Describes the air distribution in the gallery.
出处 《暖通空调》 北大核心 2008年第9期44-47,共4页 Heating Ventilating & Air Conditioning
关键词 水(冰)下玻璃廊 防结露 室外空气综合温度 冷负荷计算 underwater (ice) glass gallery, condensation prevention, outdoor sol-air temperature, cooling load calculation
  • 相关文献

参考文献3

  • 1中国有色工程设计研究总院.GB50019-2003采暖通风与空气调节设计规范[S].北京:中国计划出版社,2004.
  • 2霍夫曼.传热学[M].马庆芳,译.北京:高等教育出版社,1989
  • 3建设部工程质量安全监督与行业发展司,中国建筑标准设计研究所.民用建筑暖通空调设计技术措施暖通空调·动力[M].北京:中国建筑工业出版社,1996