期刊文献+

一起雷击220kV线路引起开关设备故障的计算分析 被引量:22

Calculation and Analysis of a Switchgear Fault Caused by Lightning Strike on 220kV Transmission Lines
在线阅读 下载PDF
导出
摘要 近几年华东地区220kV及以下电压等级的变电站和电厂发生了多起与雷击相关的开关闪络和爆炸事件,2007年7月发生了一起某220kV线路遭雷击造成一侧变电所开关闪络和另一侧变电所CT击穿的故障。笔者结合实际运行情况,利用电磁暂态程序EMTP对此故障进行了雷电侵入波过电压模拟计算,根据计算结果对故障发生原因进行了分析和研究,提出了在220kV线路进线保护段末端装设避雷器来限制雷电侵入波过电压的防范措施。 Flashovers or even explosions of switchgears fixed on substations and power plant at the voltage rank of 220 kV or below, which were caused by lightning intrusive waves, have taken place frequently in east China in recent years. In July 2007, this kind of event occurred because of lightning strike on the 220 kV transmission line, which generated the circuit breaker flashover and current transformer dielectric breakdown. This paper simulates the accident considering the running condition, and obtains the lightning over-voltages by the software EMTP. According to the over-voltage values, the reasons of the accident are analysed, and some protection methods from over-voltage due to lightning intrusive wave are presented by installing MOAs at both ends of the 220 kV transmission lines.
出处 《高压电器》 CAS CSCD 北大核心 2008年第5期428-431,共4页 High Voltage Apparatus
关键词 开关 闪络 击穿 雷电侵入波 过电压 circuit breaker flashover breakdown lightning intrusive wave over-voltage
  • 相关文献

参考文献10

二级参考文献12

  • 1GB/T11022-1999.高压开关设备和控制设备标准的共用技术要求[S].[S].,..
  • 2Li Xiao-rong, O P Malik, Zhao Zhi-da. A Practical Mathematical Model of Corona for Calculationof Transients on Transmission Lines[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1 145-1 152 .
  • 3Sandoval Carneiro. Evaluation of Corona and Line Models in Electromagnetic Transients Simulations [J]. IEEE Trans. on Power Delivery, 1991, 6(1): 334-342.
  • 4M A Al-Tai, H S B Elayyan. The Simulation of Surge Corona on Transmission Lines [J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1 360-1 368.
  • 5吴维韩.金属氧化物非线性电阻特性和应用.北京:清华大学学术专著[M].,1998..
  • 6张伟钹 何金良 高玉明.过电压防护及绝缘配合[M].北京:清华大学出版社,2002..
  • 7Sherer H R et al. Electrical structural and environmental criteria for EHV and UHV transmission lines. CIGRE,1984,Rep 22-05.
  • 8Nikitin O A, et al. Problems of lightning protection of 1 150kV power transmission line. Proc. 21 Int. Conf. on Lightning Protection, Berlin, 1992.
  • 9王兰义.日本氧化锌避雷器的发展动向[J].电瓷避雷器,1999(3):27-32. 被引量:39
  • 10宋伟新.两起断路器雷击爆炸事故的分析及探讨[J].广东电力,2000,13(5):43-44. 被引量:8