期刊文献+

太阳能光伏并网发电系统中孤岛效应的仿真研究 被引量:9

The Island Effect Simulation Research in the Solar Grid-connected PV System
在线阅读 下载PDF
导出
摘要 光伏并网发电系统除了具有过压、欠压、过频、欠频等常规保护外,还应具有一种特殊的保护功能———孤岛保护。被动式孤岛保护常采用过压欠压检测和相位突变检测相结合的方法。两种被动保护相结合能够保护绝大部分孤岛现象。但当PV系统输出功率和负载匹配时,被动式孤岛检测方法失效。因此,本文采用被动式孤岛检测和主动频率偏移(AFD)相结合的孤岛检测方法,实现了孤岛效应的无盲区检测。 Gridconnected PV system in addition to having over- voltage, under-voltage, overfrequent, less- frequent, such as conventonal protection, we must also have a special kind of protection - Gudao protection. Gudao passive protection regularly use the combine methods of over - voltage under - voltage detection and phase mutation detection. The combination of two types of passive protection to protect the vast majority of island phenomenon. However, when the PV system output power and load match, the passive detection method Gudao failure, Therefore, the use of passive and active Gudao detection frequency deviation (AFD) combining Gudao detection methods, the achievement of the island effect of the non - blind spot detection.
出处 《灯与照明》 2009年第1期59-62,共4页 Light & Lighting
关键词 并网 孤岛效应 检测 孤岛保护 grid island effect detection Gudao protection
  • 相关文献

参考文献5

  • 1IEEE recommended practice for utility interface of photovoltaic (PV) systems [ S ]. IEEE Std. 929 - 2000
  • 2Jeraputra C, Enjeti P. Development of a robust antiislanding algorithm for utility interconnection of distributed fuel cell powered generation [ J ]. IEEE Transactions on Power Electronics, 2004,1 9 (5) : 1163 - 1170
  • 3Ye Z H, Kolwalkar A, Zhang Y, et al. Evaluation of anti - islanding schemes based on nondetection zone concept [J].IEEE Transactions Power Electronics, 2004, 19 ( 5 ) : 1171 - 1176
  • 4Smith G A, Onions P A, Infield D G. Predicting islanding operation of grid connected PV inverters [J] .IEE Proceedings on Electrie Power Applications, 2000, 147(1 ) : 1 - 6
  • 5郑诗程,丁明,苏建徽,茆美琴,张国荣.光伏发电系统及其孤岛效应的仿真与实验研究[J].系统仿真学报,2005,17(12):3085-3088. 被引量:47

二级参考文献6

  • 1John Stevens, Russell Bonn, Jerry Ginn, Sigifredo Gonzalez.Development and Testing of an Approach to Anti-Islanding in Utility-Interconnected Photovoltaic Systems [Z]. 2000.
  • 2IEEE Std 929-2000. IEEE Recommended Practice for Utility Interface of Photovoltaic Systems [S]. Institute of Electrical and Electronics Engineers, Inc, New York, NY.
  • 3UL 1741, Std 1741, Static Inverter and Charge Controllers for Use in Photovoltaic Systems [S]. Underwriters Laboratories Inc,Northbrook, IL.
  • 4A Kitamura, M Dkamoto, K Hotta, etc. Islanding prevention measures: Demonstration testing at rokko test center for advanced energy systems [J]. 1993, IEEE.
  • 5G A Smith, P A Onions, D G Infield. Predicting islanding operation of grid connected PV inverters [J]. IEE Proc-Electr. Power Appl. 2000,147(1).
  • 6Math Works. Simulink-Dynamic system simulation software:User's Guide [Z]. 1992.