摘要
通过1年的现场接地网防腐蚀保护试验,并进行定期开挖观察,对比分析镀锌、缓蚀剂、外加电流阴极保护法及其联合保护的效果,并利用埋片计算腐蚀速率。结果表明外加电流阴极保护效果最好,接地网腐蚀速率由保护前的0.084 mm/a减小到0.01 mm/a左右,保护度达85%以上。
After one year's anti-corrosion field application test,with regular observation on excavating,the effects of galvanization, corrosion inhibition.impressed current cathodic protection and joint application of each other are comparatively analyzed.and corrosion rate is figured out by buried slide method.The results show that,the effect of impressed current cathodic protection is the best,the corrosion rate of substation ground grid decreases from the 0.084 mm/a before protection to about 0.01mm/a.percentage of protection is above 85%.
出处
《陕西电力》
2010年第8期39-41,共3页
Shanxi Electric Power
关键词
接地网
镀锌
缓蚀剂
外加电流
阴极保护
腐蚀速率
substation ground grid
galvanization
corrosion inhibition
impressed current
cathodic protection