摘要 对比了国内外各标准对110 kV XLPE电缆交流耐压试验时间参数选取的不同要求;通过固体电介质击穿理论的分析,提出由局部性缺陷发展逐渐导致介质击穿需要较长的发展时间。总结现场试验经验发现,除少数极为严重的缺陷会在极短时间内暴露外,大部分缺陷是从局部逐渐发展导致电缆击穿,选择5 min试验时间不足以使缺陷暴露的,而选择60 min是较为合理的。 This paper compared the different criteria in selecting the test time parameter for 110 kV cross-linked polyethylene(XLPE) cables in the different codes and standards both at home and abroad.Based on analyses in line with the solid dielectric breakdown theory,it concluded that it takes a long time for a partial fault to develop gradually to the dielectric breakdown.According to the actual site tests,except a small number of serious faults which could be exposed in a very short time,most faults,started from partial ones,turned into breakdowns slowly over time.Selection of 5 minutes as the test time is inadequate for explosion of faults,while the relatively more appropriate test time should be 60 minutes.
出处 《电网与清洁能源》 2010年第8期15-17,33,共4页 Power System and Clean Energy
基金 甘肃省电力公司重大科技项目(2008406022)
关键词 交联聚乙烯(XLPE) 交流耐压 试验时间 击穿 cross-linked polyethylene(XLPE) alternating voltagetest testtime breakdown
  • 相关文献

参考文献4

二级参考文献5

  • 1彭潜,陈俊武,梁望霖,吴云飞,袁皓.XLPE电缆工频耐压试验探讨[J].高电压技术,2005,31(5):55-55. 被引量:14
  • 2解秀余,张鹏,雒峰.110kV XLPE电缆人为机械损伤的试验[J].高电压技术,2005,31(7):78-78. 被引量:3
  • 3中国华北电力集团公司.电力设备交接和预防性试验规程[Z].北京:中国华北电力集团公司,2002..
  • 4IEC60840, Power cable with extruded insulation and their accessories for rated voltages above 30 kV (Um=36 kV) up to 150 kV(Um=170 kV)-Test methods and requirements[S], 2004.
  • 5IEC62067, Power cable with extruded insulation and their accessories for rated voltages above 150 kV(Um = 170 kV) up to 500 kV(Um = 550kV)-Test methods and requirements[S], 2001.

共引文献76

同被引文献95

引证文献13

二级引证文献121

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部