期刊文献+

安徽电网变压器油硫腐蚀研究及防护 被引量:8

Sulfur Corrosion Research and Protection of Transformer Oil in Anhui Grid
在线阅读 下载PDF
导出
摘要 针对安徽电网220kV及以上大型变压器在运行中发现的硫腐蚀问题,初步分析了产生硫腐蚀的原因、影响因素及对设备安全运行的危害;在此基础上开展了防护对策的研究,确定了硫腐蚀的最佳检测方法,提出了向运行变压器油中添加金属钝化剂以避免硫腐蚀发生的解决方案,介绍了添加金属钝化剂技术在安徽电网220kV及以上大型变压器上的具体应用情况。 To solve the problem of sulfur corrosion in large transformer of 220kV and above in Anhui power grid,the causes are analyzed,as well as influencing factor and its damage to equipment operation.Based on that,countermeasures are studied,and the sulfur corrosion optimum detection is determined,and the solution of adding the passivator to the transformer oil to avoid sulfur corrosion is proposed.Application of passivator technique to 220kV and above transformers of Anhui power grid is presented.
出处 《安徽电气工程职业技术学院学报》 2012年第1期10-14,共5页 Journal of Anhui Electrical Engineering Professional Technique College
关键词 变压器油 硫腐蚀 金属钝化剂 研究 防护 transformer oil sulfur corrosion metal passivator research protection
  • 相关文献

参考文献2

  • 1L R Lewand.The Role of Corrosive Sulfur in Transformers And Transformer Oil[]..
  • 2Motoo Tsuchie,Teruo Miyamoto.Degradation and Cupric Corrosion Caused by Corrosive Sulfur in Insulating Oil[].TIEE Japan.1995

同被引文献76

  • 1蒋良胜,施广宇.变压器铜导线硫化腐蚀问题分析[J].福建电力与电工,2006,26(3). 被引量:14
  • 2杨波,田松柏,赵杉林.不同形态硫化合物腐蚀行为的研究[J].腐蚀科学与防护技术,2004,16(6):385-388. 被引量:39
  • 3ABB公司研究报告.ABB评论,2004,(3).
  • 4孙目珍.电介质物理基础[M].广州:华南理工大学出版社,2002..
  • 5CASTLE J E,WHITFIELD T B, ALI M. The transport of copper through oil-impregnated paper insulation in electrical current transformers and busbings[J]. IEEE Electrical Insulation Magazine, 2003,19(1) : 25-29.
  • 6AKSHATHA A, ANJANA K, KUMAR R A, et al. Understanding copper corrosion due to sulphur in oil of large transformers by different approaches[C]//2012 IEEE international Conference on Condition Monitoring and Diagnosis.Bali, Indonesia: IEEE, 2012 : 336-339.
  • 7KALANTAR A, LEVIN M. Factors affecting the dissolution of copper in transformer olis[J]. Lubrication Science,2008 (20) : 223-240.
  • 8CIGRE WGA2-32.Copper sulphide in transformer insulation [C]//Cape Toun.South Africa:[s.n.], 2009:1-34.
  • 9KALANTAR A, LEVIN M. Factors affecting the dissolution of copper in transformer oils[J]. Lubrication Science,2008 (20) : 223-240.
  • 10AMIMOTO T,NAGAO E,TANIMURA J. Identification of affecting factors of copper suli-de deposition on insulating paper in oil[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2009,16(1) : 265-272.