期刊文献+

主变压器中压侧后备保护改进设计 被引量:15

Improved Design for Main Transformer Middle-voltage Side Backup Protection
在线阅读 下载PDF
导出
摘要 为降低220kV主变压器中压侧死区故障对变压器的冲击,文中通过分析220kV变电站内发生主变压器中压侧死区故障的各类故障特点,并对变压器微机保护回路进行研究,提出了在现有主变压器后备保护的基础上增设中压侧死区保护的设想。根据中压侧死区故障特征量分析并得出保护启动条件,同时根据断路器额定开断时间确定该保护动作时限,通过对主变压器微机保护二次接线的研究,实现了其在生产实际中的应用。 In order to reduce the impact of dead zone fault on transformer from the 220 kV main transformer mid-voltage side,the various type fault characteristics of main transformer mid-voltage side dead zone fault in 220 kV substation are analyzed,and the microprocessor-based protection circuit for transformer is studied.Finally,it concludes that the mid-voltage side dead zone protection should be added to the existing backup protection.After this improvement,the protection act conditions according to the analysis from the mid-voltage side dead zone fault feature and the protection action time according to the rated breaking time of the circuit breaker are inferred.Through the study on microcomputer-based protection circuit of the main transformer,the actual application in production is implemented.
机构地区 郑州供电公司
出处 《电力系统自动化》 EI CSCD 北大核心 2012年第21期118-120,共3页 Automation of Electric Power Systems
关键词 220KV主变压器 中压侧 死区故障 短路电流 后备保护 220 kV main transformer mid-voltage side dead zone fault short-circuit current backup protection
  • 相关文献

参考文献9

二级参考文献23

共引文献127

同被引文献87

引证文献15

二级引证文献48

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部