摘要 针对近几年发现的变压器在运行中铜腐蚀引起绝缘故障的问题,设计了变压器油加速热老化试验;在25#变压器新油中分别加入Cu片、Cu2O粉末和CuO粉末,加热到120℃保持48天,测试及分析不同老化时间下变压器油的微水、酸值、介质损耗因数及其变化规律,研究不同价态的铜对变压器油性能的影响。结果表明:Ⅰ价铜对变压器油微水、酸值及介质损耗的变化影响最大。 In view of the insulation failure problem caused from the copper corrosion in power transformer found recently, an accelerated thermal aging experiment was designed. After adding Cu, Cu2O and CuO into 25# new transformer oil respectively and heating to 120 ℃ and keeping for 48 days, the water content, acid value, dielectric loss factor and their change law of the transformer oil were tested under different aging time, and the effect of different valence copper on the performance of the transformer oil was studied. The results show that the effect of Cu+ on the water content, acid value and dielectric loss factor of the transformer oil is the biggest.
出处 《绝缘材料》 CAS 北大核心 2013年第6期45-48,共4页 Insulating Materials
基金 电力与交通材料保护湖南省重点实验室开放基金(2010 008) 湘潭市科技局项目(2009-0019) 湖南省大学生创新实验项目
关键词 不同价态铜 变压器油 热老化 微水 酸值 介电性能 different valence copper transformer oil thermal aging water content acid value dielectric properties
  • 相关文献

参考文献8

二级参考文献50

共引文献60

同被引文献80

  • 1石景燕.变压器油中金属杂质的隐患及处理[J].变压器,2006,43(5):44-46. 被引量:12
  • 2钱艺华,何冰.变压器油中金属含量检测及危害性分析[J].江西电力,2006,30(4):4-6. 被引量:10
  • 3DL/T984-2005 油浸式变压器绝缘老化判断导则[S],2005.
  • 4钱晖,胡旭,申积良.几台变压器油中铜含量异常的分析及处理[J].湖南电力,2007,27(5):14-16. 被引量:11
  • 5Scatiggio V T F,Maina R,Tumiatti M,et al.Corrosive sulfur induced failures in oil-filled electrical power transformers and shunt reactors[J].Transactions on Power Delivery,2009,24(3):1240-1248.
  • 6Vipper A B,Balak G M,Ponomarenko N A,et al.Catalytic effect of copper on oxidation of petroleum oil with additives[J].Chemistry and Technology of Fuels and Oils,1989,24(8):353-356.
  • 7Maina R,Tumiatti V,Pompili M,et al.Dielectric loss characteristics of copper-contaminated transformer oils[J].Transactions on Power Delivery,2010,25(3):1673-1677.
  • 8Saha T K. Review of time-domain polarization measurements for assessing insulation condition in aged transformers[J]. IEEE Transac- tions on Power Delivery, 2003, 18(4): 1293-1301.
  • 9Dumitran L M, Setnescu R, Notingher P V, et al. Method for lifetime estimation of power transformer mineral oil[J]. Fuel, 2014, 117: 756-762.
  • 10Schaut A, Autru S, Eeckhoudt S. Applicability of methanol as a new marker for paper degradation in power transformers[J]. IEEE Transac- tions on Dielectrics and Electrical Insulation, 2011, 18(2): 533-540.