期刊文献+

厂用电率测试结果修正方法 被引量:3

Discussions on correction method of measured auxiliary power consumption rate
在线阅读 下载PDF
导出
摘要 分析了火电机组厂用电率测试结果修正的原因,介绍了磨煤机、风机和给水泵厂用电率测试结果的修正计算方法。以某300MW空冷机组为例进行了厂用电率测试结果的修正计算,得到该机组实测辅机总耗电功率为24 751kW,厂用电率为8.28%,修正后的总耗电功率为24 513kW,厂用电率为8.17%。 The reasons why we need to carry out correction for measured auxiliary power consumption rate were analyzed,and the correction methods for coal mills,fans and pumps were elaborated.Moreover,a300 MW air cooling unit was taken as the example to conduct correct calculation for the measured auxiliary power consumption rate.The results show that,the actual measured total electricity consumption and auxiliary power consumption rate of this unit were 24 751 kW and 8.28%,respectively.After correction,they reduced to 24 513 kW and 8.17%.
出处 《热力发电》 CAS 北大核心 2014年第8期136-139,共4页 Thermal Power Generation
关键词 厂用电率 测试结果修正 磨煤机 风机 给水泵 总耗电功率 auxiliary power consumption rate test correction coal mill fan feedwater pump total electricity consumption