摘要
某220k V电缆线路在进行耐压试验时,加压4min发生绝缘击穿事故。为了判断事故原因,对电缆终端进行解剖试验,分析故障产生的原因,为类似电缆故障处理提供了经验。
When a 220kV cable line is withstanding voltage test, an insulation breakdown accident occurs at the curent of loading 4 minutes. In order to judge the cause of the accident, the cable terminal is dissected and the causes of the fault arc analyzed, which provides experience for similar cable fault treatment.
作者
黄友聪
方超颖
郑钟楠
谢文炳
HUANG You-cong FANG Chao-ying ZHENG Zhong-nan XIE Wen-bing(State Grid Fuj ian Province Power Co. Ltd. Electric Power Research Institute, Fuzhou 510000,127hina)
出处
《工程建设与设计》
2017年第18期60-61,共2页
Construction & Design for Engineering
关键词
电缆终端
故障分析
解剖试验
应力锥
cable terminal
fault analysis
dissection test
stress cone