某数据中心机房热环境的实验研究 被引量:1

Field Study of the Thermal Environment of a Data Center
在线阅读 下载PDF
导出
摘要 随着科技的高速发展,数据中心的规模也逐渐增加,而数据中心内出现的局部过热、温度分布不均等问题也越来越引起人们的关注。本文以武汉市某小型数据中心机房为例,利用专业实验仪器对机房内关键位置(地板送风口、空调回风口、机柜进出口、某些具体测点)的风速风温进行测量。并以该实测数据为依据,对机房内热环境进行分析。本文分析结果可为该机房后续的节能优化设计提供理论依据与建议。 With the rapid development of science and technology, the scale of data center has gradually increased. However, the issue of local overheating and uneven distribution of temperature in the data center has attracted more and more attention. This paper takes a data center in Wuhan as an example, the air speed and temperature of typical location (perforated tiles in the cold aisle, return air vent of the air conditioner, inlet and outlet of the rack, as well as some specific measurement points) in the data center were measured via the professional instruments. Based on the experimental data, the thermal environment of the data center was analyzed. The analysis results can provide the theoretical basis and suggestion for the design of the energy saving optimization design.
作者 张雪娇 周军莉 陈祥令 龚辉 甘婷 邓勤犁 郑洪波 ZHANG Xuejiao;ZHOU Junli;CHEN Xiangling;GONG Hui;GAN Ting;DENG Qinli;ZHENG Hongbo(School of Civil Engineering and Architecture, Wuhan University of Technology;Wuhan Metro Group Co., Ltd.;Schneider Electric (China) Information Technology Co., Ltd.)
出处 《建筑热能通风空调》 2019年第3期61-64,27,共5页 Building Energy & Environment
基金 国家自然科学基金(No.51608405) 武汉地铁集团有限公司(III-JZ-16-103)项目
关键词 数据中心 热环境 实验研究 结果分析 data center thermal environment experimental study result analysis