期刊文献+

水电厂消防水管腐蚀调查研究 被引量:5

Investigation on Fire Hose Corrosion in Hydropower Plants
在线阅读 下载PDF
导出
摘要 由于水电厂消防用水直接取自江河原水,未进行相应的杀菌和水质检测试验。加上消防管道内水质长期不流通,数年后开始腐蚀泄露,影响电厂稳定运行,形成安全隐患。本次选取两个水电厂进行消防水管腐蚀调查研究对象,对消防管样和水样进行X荧光射线检测、电镜能谱分析、原水水质分析。将腐蚀现象与试验数据结合研究,得出A厂的消防水管泄露主要是由微生物的腐蚀所引起,B厂的消防水管泄露主要是由高浓度Cl^-离子的点蚀所引起。 The fire water of hydropower plant is provided from the river directly,without any disinfection and testing.Then the fire hose has been corroded and leaked out when the water locked inside for several years.It will threaten the safe operation of hydropower plants.Choosing the samples from two different hydropower plants to investigation,the samples were analyzed by X-ray testing,EDAX and water quality test.The calculation result showed that A Plant fire hose leakage was mainly caused by microbial corrosion,and the B Plant was mainly caused by Cl^-corrosion.
作者 陆泓羽 何常胜 何智华 郭绍旭 王明帆 LU Hong-yu;HE Chang-sheng;HE Zhi-hua;GUO Shao-xu;WANG Ming-fan(Yunnan Electric Power Test&Research Institute Group Co.,Ltd.,Yunnan Kunming 650217,China)
出处 《广州化工》 CAS 2020年第23期135-136,192,共3页 GuangZhou Chemical Industry
关键词 水电厂 消防水管 微生物腐蚀 Cl^-离子腐蚀 hydropower plants fire hose microbial corrosion Cl^-corrosion
  • 相关文献

参考文献4

二级参考文献88

共引文献89

同被引文献36

引证文献5

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部