期刊文献+

基于损耗因数的干式串联电抗器匝间绝缘状态监测技术 被引量:2

Inter-Turn Insulation State Monitoring Technology of Dry-Type Series Reactor Based on Loss Factor
在线阅读 下载PDF
导出
摘要 无功补偿成套装置中的串联电抗器采用固体绝缘结构,针对其运行中匝间短路故障频发且检测手段不足问题,提出了基于损耗因数的串联电抗器匝间绝缘监测技术。分析了串联电抗器发生匝间短路故障的原因,建立电抗器匝间短路等效电路,针对其故障特征研究了电抗器匝间短路监测的技术方案,并通过有限元仿真软件验证了所提方案的可行性和有效性。 The series reactor in the complete set of reactive power compensation device adopts a solid insulation structure.Aiming at the problems of frequent occurrence of inter-turn short-circuit faults of series reactors in reactive power compensation equipment and insufficient detection methods,this paper proposed a monitoring technique for inter-turn insulation of series reactors based on loss factor.And the cause of the inter-turn short-circuit fault of the series reactor was briefly analyzed;then,the equivalent circuit of the inter-turn short circuit of the reactor was established,and the technical scheme of the inter-turn short circuit monitoring of the reactor was studied according to its fault characteristics;Finally,the feasibility and effectiveness of the proposed scheme are verified by finite element simulation software.
作者 谢同平 于洋 刘兴华 鲁尧 咸日常 XIE Tong-ping;YU Yang;LIU Xing-hua;LU Yao;XIAN Ri-chang(Zibo Power Supply Company of State Grid Shandong Electric Power Corporation,Zibo 255000,China;School of Electrical and Electronic Engineering,Shandong University of Technology,Zibo 255049,China)
出处 《电工电气》 2021年第1期47-50,共4页 Electrotechnics Electric
基金 国网山东省电力公司科技项目(5206031900FR)。
关键词 串联电抗器 匝间绝缘 损耗因数 监测技术 series reactor inter-turn insulation loss factor monitoring technology
  • 相关文献

参考文献9

二级参考文献98

共引文献111

同被引文献31

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部