摘要
针对海南地区游泳馆的特点,结合海南省儋州市某体育中心游泳馆实际案例,通过对热湿负荷的详细计算,最后确定了整个游泳馆的空调系统形式和除湿方式,并通过对通风除湿设计中室外计算含湿量值的分析,认为在不保证小时数的情况下用含湿量计算风量更为合理。根据游泳池和坐席区的不同温湿度要求,进行了气流组织的分区设置,合理设计了相应的空调、通风及供暖系统。在一个大空间中营造了两个不同的小气候环境,满足了观众区、池区不同场所的舒适性要求。
According to the characteristics of the natatorium in Hainan Province,combined with the actual case of the natatorium in a sports center in Danzhou City,Hainan Province,through the detailed calculation of the heat and humidity load,the air conditioning system mode of the natatorium and the dehumidification mode of the whole natatorium are finally determined,and the value of the outdoor calculation moisture content in the design of ventilation and dehumidification is analyzed,It is considered that it is more reasonable to use the moisture content which is not guaranteed for hours to calculate the ventilation capacity.According to the different temperature and humidity requirements of the pool area and the stand,the air distribution is divided into different zones,and the corresponding air conditioning,ventilation and heating systems are designed reasonably.In a large space,two different microclimate environments are created to meet the comfort requirements of different places in the audience area and pool area.
作者
贾瑜
蔡潇涵
Jia Yu;Cai Xiaohan
出处
《洁净与空调技术》
2021年第2期90-93,共4页
Contamination Control & Air-Conditioning Technology
关键词
游泳馆
通风除湿
防结露
气流组织
通风量
Natatorium
Ventilation drying
Anti-condensation
Air distribution
Ventilation quantity