期刊文献+

一起35 kV断路器操作机构故障分析及处理

Analysis and Treatment of a 35 kV Circuit Breaker Operating Mechanism Fault
在线阅读 下载PDF
导出
摘要 介绍了一起35 kV断路器操作机构故障,通过试验分析、解体检查,指出操作机构受潮锈蚀是断路器拒分、合闸线圈和整流模块烧损的主要原因,更换受损部件后的断路器机械特性参数均合格,投运后运行良好。最后,针对此类问题的分析与处理提出了建议,为今后处理同类型的开关柜缺陷提供了经验。 This paper introduces a fault of 35 kV circuit breaker operating mechanism.Through test analysis and disassembly inspection,it is pointed out that the damp and corrosion of operating mechanism is the main cause of circuit breaker refusing to open,closing coil and rectifier module burning.The mechanical characteristic parameters of circuit breaker after replacing damaged parts are qualified and operate well after putting into operation.Finally,some suggestions are put forward for the analysis and treatment of such problems,which provides experience for dealing with the defects of the same type of switchgear in the future.
作者 庄先涛 袁霞 陈杰 Zhuang Xian-tao;Yuan Xia;Chen Jie
出处 《电力系统装备》 2021年第23期136-137,共2页 Electric Power System Equipment
关键词 断路器 操作机构 受潮锈蚀 机械特性 circuit breaker operating mechanism damp and rust mechanical property
  • 相关文献

参考文献7

二级参考文献56

  • 1谢雷钢,张骁萌,闵超.替代高压电器设备用环氧树脂的热塑性材料特性研究[J].高压电器,2020,56(2):210-214. 被引量:5
  • 2庞文龙,吴细秀,吴士普,杨芷宁,杨馨,侯慧.330 kV SF6/N2混合气体介质绝缘母线的紧凑化设计[J].高电压技术,2020,46(3):1044-1051. 被引量:5
  • 3李兴文,贾申利,张博雅.气体开关电弧物性参数计算及特性仿真研究与应用[J].高电压技术,2020,46(3):757-771. 被引量:38
  • 4郭琳,黄兴泉,张欲晓,安江英,郭强.高压断路器操作弹簧断裂及分析[J].电网技术,2006,30(S1):214-216. 被引量:4
  • 5Aaufermann.配电盘的数字技术——新一代配电盘设计的关键[A]..第14届国际供电会议论文集[C].中国电机工程学会供电专委会,1998..
  • 6Swerner.配电站在竞争环境中的创新[A]..第15届国际供电会议论文集[C].中国电机工程学会供电专委会,2000..
  • 7Gperrissin.开发一种国际中压开关装置系列的创造性方法[A]..第13届国际供电会议论文集[C].中国电机工程学会供电专委会,1996..
  • 8Mmarchi.耐内部电弧的开关装置,电弧模拟和有效保护[A]..第14届国际供电会议论文集[C].中国电机工程学会供电专委会,1998..
  • 9Mbinnendijk.中压开关装置中内部电弧的预防和控制[A]..第14届国际供电会议论文集[C].中国电机工程学会供电专委会,1998..
  • 10Kjakob.空气绝缘及气体绝缘开关装置用新型智能数字式电弧检测系统[A]..第14届国际供电会议论文集[C].中国电机工程学会供电专委会,1998..