摘要 以某办公建筑为例,研究了工位送风对工作区热舒适的影响和节能潜力。利用CFD数值模拟,对不同气流组织形式人员工作区的温度场、速度场进行研究,并对不同风口的耗冷量进行了对比。结果表明,个性化工位送风在优化出风风速基础上提升人员热舒适,同时实现耗冷量降低27.6%。 Taking an office building as an example,research on the influence of task air supply on the thermal comfort and energy-saving potential of the work area.Using CFD numerical simulation,the temperature field and velocity field of personnel working area with different air distribution are studied,and the cooling consumption of different tuyeres is compared.The results show that personalized ventilation can improve thermal comfort of personnel on the basis of optimizing the outlet velocity,and reduce the cooling consumption by 27.6%.
作者 钟辉智 刘联华 周航 Zhong Huizhi;Liu Lianhua;Zhou Hang(China Southwest Architectural Design and Research Institute Co.,Ltd,Chengdu,610042)
出处 《制冷与空调(四川)》 2022年第3期440-443,495,共5页 Refrigeration and Air Conditioning
基金 国家重点研发计划政府间国际科技创新合作重点专项“净零能耗建筑关键技术研究与示范”项目(19YFE0100300-11) 四川省科技计划重点研发项目“绿色建筑运行性能提升关键技术研究”(2020YFS0060)。
关键词 气流组织 数值模拟 工位送风 节能 Air distribution Numerical simulation Task air supply Energy saving
  • 相关文献

参考文献2

二级参考文献24

  • 1端木琳,舒海文,杜国付.工位空调送风气流微环境评价[J].暖通空调,2004,34(12):7-9. 被引量:14
  • 2荆有印,齐晓唯,周春丽,郑国忠,王峥.空调羽毛球场馆内三维紊流流动的数值模拟与研究[J].制冷与空调,2005,5(3):41-43. 被引量:9
  • 3Melikov A K, Nielsen J B. Local thermal comfort due to draft and vertical temperature difference in rooms with displacement ventilation. In: ASHRAE Trans.1989, 95. 1050-1057
  • 4Stymne H, Sandberg M, Mattsson M. Dispersion patter of contaminants in a displacement ventilation room. In: Proceedings of the 12th AIVC Conference,1991
  • 5Heinemeier K E, Schiller G E, Benton C C. Task conditioning for the workplace: issues and challenges. In: ASHRAE Trans. 1993, 99. 678- 689
  • 6Fanger P O. Human requirements in future air conditioned environments: a search for excellence. In:Proceedings of the 3rd ISHVAC, Shenzhen, 1999,1.86 - 92
  • 7Faulkner D, Fisk W J, Sullivan D P. Indoor airflow and pollutant removal in a room with desktop ventilation. In: ASHRAE Trans. 1993, 99(2). 750 -758
  • 8Bauman F S, Zhang H, Arens E A, et al. Localized comfort control with a desktop task conditioning system: laboratory and field measurements. In:ASHRAE Trans. 1993, 99(2). 733 - 749
  • 9ASHRAE standard 62 - 1989. Ventilation for acceptable indoor air quality
  • 10European committee for standardization. CEN CR1752. Ventilation for buildings-design criteria for the indoor environment. 1998