期刊文献+

无刷励磁机两点接地对DNC检测的影响研究

The Influence Study for Non-Conduction Detection when the Exciter is Grounded at Two Points
在线阅读 下载PDF
导出
摘要 无刷励磁机DNC(Non-Conduction Detection)装置通过检测励磁机旋转电枢出线上的脉冲电流的方法检测旋转二极管不导通故障。当检测到断一相故障时发出报警信号,断两相故障时发出跳机信号。某核电站机组功率运行期间经受一个瞬态后,DNC装置先发出断一相故障报警信号,几秒后又发出断两相故障跳机信号,造成机组跳机。经停机后检查,励磁机未发生断两相故障,仅断一相,但磁极存在接地故障。本文通过分析无刷励磁机励磁绕组两点接地对DNC装置检测的影响,解释了DNC装置误发断两相故障跳机信号的原因。 The non-conduction detection device of the brushless exciter detects the non conduction fault of the rotating diode by detecting the pulse current on the outgoing line of the rotating armature of the exciter.When one phase failure is detected,an alarm signal is sent;and when two-phase failure is detected,a trip signal is sent.After the unit of a nuclear power plant experienced a transient during power operation,the DNC device first sent out a phase failure alarm signal,and then sent out a phase failure trip signal a few seconds later,resulting in unit trip.Through inspection after shutdown,the exciter did not break two phases,only one phase,but the magnetic pole had grounding fault.By analyzing the influence of two-point grounding of excitation winding of the brushless exciter on the detection of DNC device,this paper explains the reason why DNC device mistakenly sends out two-phase fault tripping signal.
作者 沈红 段琰璞 向超 SHEN Hong;DUAN Yanpu;XIANG Chao(State Nuclear Power Demonstration Plant Co.,Ltd.,Rongcheng of Shandong Prov.264300,China;China Nuclear Power Engineering Co.,Ltd.Shenzhen of Guangdong Prov.518124,China)
出处 《核科学与工程》 CAS CSCD 北大核心 2023年第1期79-84,共6页 Nuclear Science and Engineering
关键词 无刷励磁机 磁极接地 DNC Brushless exciter Magnetic pole grounding DNC
  • 相关文献

参考文献4

二级参考文献4

共引文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部