计及界面电荷和极性效应的油纸复合绝缘非线性电路等效模型 被引量:2

Equivalent Nonlinear Circuit Model with Interface Charge and Polarity Effect for Oil-Paper Composite Insulation
在线阅读 下载PDF
导出
摘要 换流变压器是特高压直流输电工程中的关键设备,换流变压器油纸复合绝缘的界面处在直流电压下易积聚电荷,诱发局部放电甚至击穿。当前对于界面电荷的积聚分布,多采用传统的阻容模型进行计算,存在较大的误差。该文提出一种简易的非线性电路等效模型,首先,分别测量变压器油和油浸纸板的电容、电阻参数与极化电流,获得油纸的拓展Debye模型;其次,在拓展Debye模型的基础上,将变压器油和油浸纸板的恒定电阻模型改为随电场变化的非线性模型,并加入反映极性效应的界面势垒限制电流源,以此建立等效模型;最后,将电路等效模型仿真结果与实际测量结果进行对比。结果表明,与实际测量结果相比,该等效模型具有良好的适用性。该文模型为油纸绝缘的电场分布、界面电荷积聚量的计算提供了一种准确度较高的简便方法。 In the operation of a converter transformer,the interface of its oil-paper composite insulation is prone to charge accumulation under DC voltage.A simple non-linear equivalent circuit model is proposed based on the extended Debye model in this paper,which can calculate the electric field distribution and interface charge amount of oil-paper insulation more easily and accurately.Firstly,the capacitance and resistance parameters of the transformer oil and the oil-immersed paperboard are separately measured,and the electric field strength in the oil is measured based on the Kerr effect method at applied voltages from 5 to 25 kV respectively.The electric field distribution in the oil-paper composite insulation is calculated for different applied voltages as well as different voltage polarities,and the measured results are compared with the calculated results from the RC model.Secondly,the conductivity of the transformer oil and oil-immersed paperboard are measured under different electric field strength to establish a non-linear conductivity model for the oil-paper composite insulation.Then the polarisation currents of the transformer oil and oil-immersed paperboard are separately measured and fitted to extract the branch parameters of extended Debye model.Finally,the interface potential barriers are derived from the measured polarisation currents,and the polarity determined interface potential barrier is then added to the model to limit the current through the interface,thus establishing a non-linear equivalent circuit model for the transformer oil and oil-impregnated paperboard where the resistances are the electric field strength dependent.The electric field distribution in the oil-paper composite insulation calculated by the established non-linear equivalent model is compared with those by the RC model,extended Debye model and actual measured results.The time to steady state calculated by the equivalent model is reduced to about 500 s,which is shorter than that calculated by the RC and Debye models,and is closer to the measured results.As regards the steady state electric field in oil at different applied voltages,it can be seen that the error between those by the equivalent model and measurment is less than 5%for both positive and negative polarities.The error between the electric field in oil calculated by the equivalent model and the measured results is greatest at DC voltage of 25 kV,but the maximum error is 4.8%.These indicate that the accuracy of this model is greatly improved compared to the RC and series extended Debye model.Comparing the results of the three models with the measured values for positive and negative polarities,the equivalent model is much closer to the measured values than the RC and extended Debye model,and just the equivalent model reflects a polarity effect.The absolute value of the measured negative interface charge amount at 25 kV is merely 1.07%higher than the proposed equivalent model calculation,and the measured positive interface charge amount is 0.95%higher than the proposed equivalent model calculation.The following conclusions can be drawn from the above:(1)Compared with the RC and extended Debye model,the dynamics of electric field distribution of the oil-paper insulation calculated by the proposed model reach the steady state faster and is closer to the measured situation.(2)The proposed model takes into account the polarity determined interface barrier to limit the current through the interface,so its calculation can reflect the polarity effect and the error between the calculated and measured electric field is less than 5%.(3)The model has incorporated the influence of nonlinear conductivity,relaxation polarisation and interfacial potential barrier limiting current,so it has a good applicability to the calculation of the interfacial charge of oil-paper insulation under different conditions more easily and accurately.
作者 黄猛 李怡然 吴延宇 陈良炯 齐波 Huang Meng;Li Yiran;Wu Yanyu;Chen Liangjiong;Qi Bo(State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources,North China Electric Power University,Beijing,102206,China)
出处 《电工技术学报》 EI CSCD 北大核心 2024年第11期3422-3432,共11页 Transactions of China Electrotechnical Society
基金 国家自然科学基金(51807062) 北京市自然科学基金(3212035)资助项目。
关键词 油纸绝缘 界面电荷 界面极化 拓展Debye模型 电路等效模型 Oil-paper insulation interface charge interface polarization extended Debye model equivalent circuit model
  • 相关文献

参考文献14

二级参考文献195

  • 1田杰,段绍辉,许昊,汤明杰,张冠军.温度及老化状态对油纸绝缘时域介电响应特性影响的实验研究[J].中国电机工程学报,2012,32(S1):69-75. 被引量:27
  • 2聂德鑫,沙彦超,周远翔,黄猛,卢理成,黄治华.油纸绝缘直流极性反转试验及局部放电测量[J].变压器,2015,52(3):51-55. 被引量:6
  • 3刘枫林,徐魏.石蜡基和环烷基变压器油的性能比较[J].变压器,2004,41(7):27-30. 被引量:39
  • 4王梦云.110kV及以上变压器事故统计与分析[J].供用电,2005,22(2):8-12. 被引量:11
  • 5李永东,何锋,刘纯亮.轴对称平板二极管空间电荷限制流的2维效应[J].强激光与粒子束,2005,17(6):913-916. 被引量:6
  • 6Peter M, Marc J. Space charge measurements on impregnated paper: a review of the PEA method and a discussion of results [J]. IEEE Electrical Insulation Magazine* 1997,13(3) : 26-35.
  • 7Ciobanu R, Schreiner C,Pfeiffer W,et al. Space charge evolution in oil-paper insulation for DC cables application[C] // Proceedings of 14th International Conference on Dielectric Liquids. Graz, Austria: IEEE, 2002: 321-324.
  • 8Liu R, Tomkvist C. Charge storage and transport in oil-impregnated pressboard at polarity reversal under HVDC[C] // Proceedings of 1995 Conference on Electrical Insulation and Dielectric Phenomena. Virginia Beach, USA: IEEE, 1995 : 33-36.
  • 9Mas P,Touchard G,Moreau O. Correlation between temperature gradient and space charge in an oil impregnated pressboard submitted to an electric field[C]//1999 Conference on Electrtcal Insulation and Dielectric Phenomena. Austin, USA; IEEE, 2007: 789-793.
  • 10Liu R, Wahlstom G. Measurements of the DC electric field in liquid imprgnated pressboard using the pressure wave propagation technique[C]//Conference Record of the 1994 IEEE International Symposium on Electrical Insulation. Pittsburgh, USA: IEEE, 1994: 5-8.

共引文献128

同被引文献33

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部