期刊文献+

中性点经消弧线圈接地系统单相接地故障暂态电流分析 被引量:15

Analysis of transient current when single-phase grounding in electric power system whose neutral point connects to the ground via arc-suppression coil
在线阅读 下载PDF
导出
摘要 通过对中性点经消弧线圈接地系统单相接地时零序暂态电流的频域分析和时域分析 ,得出接地导线中零序暂态电流的峰值比健全线路中零序暂态电流的峰值大许多 ,比较峰值的大小可以识别故障线路 ,同时得出零序暂态电流的方向是不确定的 ,不宜采用零序暂态电流的方向作为选线判据。 By analysis of zero sequence transient current when single phase grounding in electric power system whose neutal point connects to the ground via arc suppression coil, that maximum of zero sequence transient current in grounding wire is much greater than in well_condition circuit is concluded. By comparing the size of maximum the malfunction circuit can be found out. At the same time it is concluded that the direction of zero sequence transient current is unknown and should not be used for the basis of line_selection.
机构地区 辽宁工学院
出处 《继电器》 CSCD 北大核心 2002年第11期16-18,共3页 Relay
关键词 中性点 消弧线圈 接地系统 单相接地 故障 暂态电流分析 arc suppression coil transient current line selection